![Honeywell AUTOMATIC CONTROL Engineering Manual Download Page 301](http://html.mh-extra.com/html/honeywell/automatic-control/automatic-control_engineering-manual_149859301.webp)
ENGINEERING MANUAL OF AUTOMATION CONTROL
BUILDING AIRFLOW SYSTEM CONTROL APPLICATIONS
291
Figure 49 shows a similar example of negative space
pressurization utilizing direct pressure control. If the airflow
through the hood is 1000 cfm and the pressure control reduces
the supply airflow when the door is opened, the average velocity
through openings drops from 400 fpm to 48.8 fpm.
CRACK AREA = 0.5 FT 2
SUPPLY
0-800 CFM
DOOR
2
20 FT
FUME HOOD
EXHAUST
1000 CFM
DOOR CLOSED
= 400 FPM
DOOR OPENED
= 48.8 FPM
C2639
VELOCITY =1000
20.5
÷
VELOCITY = 200
0.5
÷
DIFFERENTIAL = EXHAUST– SUPPLY
= 200 CFM
DIFFERENTIAL = EXHAUST– SUPPLY
= 1000 CFM
Fig. 48. Direct Pressure Control.
M12216
SUPPLY
AIR
SUPPLY
AIR TO
LAB
GENERAL
EXHAUST
AIR
EXHAUST
AIR
FUME
HOOD
DAMPER
ACTUATOR
SUPPLY
AIR TO
CORRIDOR
DIFFERENTIAL
PRESSURE
SENSOR
VELOCITY
SENSOR
SUPPLY AIR
DAMPER
ACTUATOR
EXHAUST AIR
DAMPER ACTUATOR
AIRFLOW
SENSOR
LAB AIRFLOW
CONTROLLER PANEL
Fig. 49. Direct Space Pressure Control Example
with Door Closed and Open.
When a door is opened, the space pressure control responds
by reducing the supply airflow to zero and/or increasing general
exhaust flow. Replacement air for the space that is being
exhausted migrates from adjacent areas through the doorway
and cracks. The supply system for the adjacent area must replace
this air in order to maintain a positive building pressurization.
The significant issues are 1) how fast can the room
pressurization system respond to upset (a door opening or
several hoods being closed at once) and 2) what is the impact
on adjacent areas and the rest of the building. Because of the
inherent lag of direct pressure control systems (the time it takes
the differential pressure sensor to know that several hoods have
been closed) the lab can go into a positive pressure mode for a
short period of time. Further, with extended door openings and
other breaches it is possible for a direct pressure based system
to call for amounts of exhaust air which may be drawn
excessively from the adjacent spaces. This has the potential for
cascading air flow and pressure effects throughout the building.
For reasons of speed and stability, volumetric tracking control
is becoming the more accepted method of pressurization control
in lab spaces.
Direct pressure control remains a viable alternative, especially
in lab spaces that are sealed tightly, where there is sufficient
building supply air and good lab operation protocols.
Summary of Contents for AUTOMATIC CONTROL
Page 4: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL iv ...
Page 6: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL vi ...
Page 11: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 1 CONTROL SYSTEMS FUNDMENTALS ...
Page 12: ......
Page 46: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 36 ...
Page 66: ...PSYCHROMETRIC CHART FUNDAMENTALS 56 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 128: ...ENGINEERING MANUAL OF AUTOMATION CONTROL ELECTRIC CONTROL FUNDAMENTALS 118 ...
Page 158: ...MICROPROCESSOR BASED DDC FUNDAMENTALS 148 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 210: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL BUILDING MANAGEMENT SYSTEM FUNDAMENTALS 200 ...
Page 440: ...ENGINEERING MANULA OF AUTOMATIC CONTROL INDIVIDUAL ROOM CONTROL APPLICATIONS 430 ...
Page 516: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 506 Notes ...
Page 517: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 507 Notes ...
Page 518: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 508 ...