PNEUMATIC CONTROL FUNDAMENTALS
ENGINEERING MANUAL OF AUTOMATIC CONTROL
74
Figure 25 shows a typical application of a thermostat and
velocity controller on a Variable Air Volume (VAV) terminal
unit with hot water reheat. The thermostat senses a change in
room temperature and resets the velocity setpoint of the
velocity controller. The controller repositions the VAV damper
to increase or decrease airflow accordingly. If a change in duct
static pressure modifies the flow, the controller repositions the
actuator to maintain the correct flow. The reheat valve operates
only when the thermostat has reset the velocity setpoint down
to minimum airflow and the thermostat calls for heating.
M
VELOCITY
SENSOR IN
DUCTWORK
VAV BOX
DAMPER
DAMPER
ACTUATOR
VELOCITY
CONTROLLER
VAV BOX
REHEAT VALVE
ROOM
THERMOSTAT
M10296
Fig. 25. VAV Box Velocity Controller Control System.
ACTUATORS AND FINAL CONTROL ELEMENTS
A pneumatic actuator and final control element such as a
valve (Fig. 26) or damper (Fig. 27) work together to vary the
flow of the medium passing through the valve or damper. In
the actuator, a diaphragm and return spring move the damper
push rod or valve stem in response to changes in branchline
pressure.
Fig. 26. Pneumatic Actuator and Valve.
C2611
DAMPER
AIRFLOW
PUSH
ROD
DAMPER
ACTUATOR
SPRING
PISTON
ROLLING
DIAPHRAGM
BRANCH
LINE
Fig. 27. Pneumatic Actuator and Damper.
ACTUATORS
GENERAL
Pneumatic actuators position damper blades and valve
stems. A damper actuator typically mounts on ductwork or on
the damper frame and uses a push rod and crank arm to position
the damper blades (rotary action). A valve actuator mounts on
the valve body and positions the valve stem directly (linear
action) for a globe valve or rotary action via linkage for a
butterfly valve. Valve actuator strokes typically are between
one-quarter and one and one-half inch. Damper actuator
strokes range from one to four inches (longer in special
applications). In commercial pneumatic actuators, air pressure
positions the actuator in one direction and a spring returns it
the other direction.
Valve actuators are direct or reverse acting. Damper actuators
are direct acting only. A direct-acting actuator extends on an
increase in branchline pressure and retracts on a decrease in
pressure. A reverse-acting actuator retracts on an increase in
branchline pressure and extends on a decrease in pressure.
Pneumatic valve and damper actuator assemblies are termed
“normally open” or “normally closed.” The normal position is
the one assumed upon zero actuator air pressure. Three-way
valves have both normally open (N.O.) and normally closed
(N.C.) ports.
SPRING RANGES
Springs used in valve and damper actuators determine the
start pressure and pressure change required for full movement
of the actuator from open to closed, or from closed to open.
Actuators designed for special applications can move through
the full range, open to closed or closed to open, on a limited
change in pressure from the controller. Such actuators can
BRANCH
LINE
SPRING
VALVE
STEM
INLET
FLOW
OUTLET
FLOW
DIAPHRAGM
VALVE
ACTUATOR
VALVE
M10361
Summary of Contents for AUTOMATIC CONTROL
Page 4: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL iv ...
Page 6: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL vi ...
Page 11: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 1 CONTROL SYSTEMS FUNDMENTALS ...
Page 12: ......
Page 46: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 36 ...
Page 66: ...PSYCHROMETRIC CHART FUNDAMENTALS 56 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 128: ...ENGINEERING MANUAL OF AUTOMATION CONTROL ELECTRIC CONTROL FUNDAMENTALS 118 ...
Page 158: ...MICROPROCESSOR BASED DDC FUNDAMENTALS 148 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 210: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL BUILDING MANAGEMENT SYSTEM FUNDAMENTALS 200 ...
Page 440: ...ENGINEERING MANULA OF AUTOMATIC CONTROL INDIVIDUAL ROOM CONTROL APPLICATIONS 430 ...
Page 516: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 506 Notes ...
Page 517: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 507 Notes ...
Page 518: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 508 ...