![Honeywell AUTOMATIC CONTROL Engineering Manual Download Page 136](http://html.mh-extra.com/html/honeywell/automatic-control/automatic-control_engineering-manual_149859136.webp)
ENGINEERING MANUAL OF AUTOMATION CONTROL
ELECTRONIC CONTROL FUNDAMENTALS
126
Fig. 10. Capacitance Type Relative Humidity Sensor.
A relative humidity sensor that generates changes in both
resistance and capacitance to measure moisture level is
constructed by anodizing an aluminum strip and then applying
a thin layer of gold or aluminum (Fig. 11). The anodized
aluminum has a layer of porous oxide on its surface. Moisture
can penetrate through the gold layer and fill the pores of the
oxide coating causing changes in both resistance and
capacitance which can be measured by an electronic circuit.
Fig. 12. Capacitance Type RH Sensor with Integral
Temperature Compensation Sensor.
CONDENSATION AND WETTING
Condensa tion occur s whene ver the sensor s surf ace
temper atur e dr ops below the de w point of the sur rounding air ,
even if onl y momentar ily. When oper ating a t levels of 95% rh
and a bove small temper atur e chang es can cause condensa tion.
Under these conditions where the ambient temperature and the
dew point ar e ver y close, condensa tion for ms quic kly, but the
moistur e tak es a long time to e vapor ate. Until the moistur e is
gone the sensor outputs a 100% rh signal.
When oper ating in high rh (90% and a bove), consider these
str ategies:
1. Maintain good air mixing to minimize local temperature
fluctuations.
2. Use a sinter ed stainless steel f ilter to pr otect the sensor
from splashing . A hydr ophobic coa ting can also suppr ess
condensation and wetting in rapidly saturating/
desatur ating or splash pr one environment.
3. Hea t the rh sensor a bove the ambient de w point
temperature.
NOTE: Heating the sensor changes the calibration and
makes it sensitive to thermal disturbances such
as airflow.
Quartz Crystal Relative Humidity Sensor
Sensors that use changes in frequency to measure relative
humidity (Fig. 13) can use a quartz crystal coated with a
hygroscopic material such as polymer plastic. When the quartz
crystal is energized by an oscillating circuit, it generates a
constant frequency. As the polymer material absorbs moisture
and changes the mass of the quartz crystal, the frequency of
oscillation varies and can be measured by an electronic circuit.
Most relative humidity sensors require electronics at the
sensor to modify and amplify the weak signal and are referred
to as transmitters. The electronic circuit compensates for the
effects of temperature as well as amplifies and linearizes the
measured level of relative humidity. The transmitters typically
provides a voltage or current output that can be used as an input
to the electronic controller.
Fig. 11. Impedance Type Relative Humidity Sensor.
TEMPERATURE COMPENSATION
Both temper atur e and per cent rh ef fect the output of all
absor ption based humidity sensor s. Applica tions calling f or
either high accur acy or wide temper atur e oper ating r ang e
requir e temper atur e compensa tion. The temper atur e should be
made as c lose as possib le to the rh sensor s acti ve ar ea. This is
especially true when using rh and temperature to measure
dewpoint. F igur e 12 shows an rh sensor with the temper
atur e
sensor mounted directly on the substrate.
ELECTRODE
ANODIZED
ALUMINUM STRIP
POROUS
OXIDE LAYER
ELECTRODE
THIN
GOLD LAYER
C3101
B. MOISTURE SENSITIVE MATERIAL BETWEEN ELECTRODE PLATES
AND THIRD CONDUCTIVE PLATE.
A. MOISTURE SENSITIVE MATERIAL BETWEEN ELECTRODE PLATES.
WIRES TO CONTROLLER
OR SENSING CIRCUIT
MOISTURE
SENSITIVE
POLYMER
GOLD FOIL OR OTHER
TYPE OF ELECTRODE PLATES
WIRES TO CONTROLLER
OR SENSING CIRCUIT
C3100
GOLD FOIL OR
OTHER TYPE OF
ELECTRODE PLATES
MOISTURE
SENSITIVE
POLYMER
ULTRA THIN LAYER OF
CONDUCTIVE MATERIAL
PROTECTIVE
POLYMER
POROUS
PLATINUM
DIELECTRIC
POLYMER
CERAMIC
SUBSTRATE
ELECTRODE
FINGERS
1000 OHM
PLATINUM RTD
M10685
Summary of Contents for AUTOMATIC CONTROL
Page 4: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL iv ...
Page 6: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL vi ...
Page 11: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 1 CONTROL SYSTEMS FUNDMENTALS ...
Page 12: ......
Page 46: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 36 ...
Page 66: ...PSYCHROMETRIC CHART FUNDAMENTALS 56 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 128: ...ENGINEERING MANUAL OF AUTOMATION CONTROL ELECTRIC CONTROL FUNDAMENTALS 118 ...
Page 158: ...MICROPROCESSOR BASED DDC FUNDAMENTALS 148 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 210: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL BUILDING MANAGEMENT SYSTEM FUNDAMENTALS 200 ...
Page 440: ...ENGINEERING MANULA OF AUTOMATIC CONTROL INDIVIDUAL ROOM CONTROL APPLICATIONS 430 ...
Page 516: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 506 Notes ...
Page 517: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 507 Notes ...
Page 518: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 508 ...