ENGINEERING CMANUAL OF AUTOMATION CONTROL
AIR HANDLING SYSTEM CONTROL APPLICATIONS
214
SPECIFICATIONS
See FAN SYSTEM START-STOP CONTROL
.
Anytime the supply fan runs, the OA, EA, and RA dampers
shall be modulated by an MA PID control loop to satisfy the
MA temperature setpoint down to a minimum ventilation
position.
PSYCHROMETRIC ASPECTS
In the following chart it is assumed that:
1. The manual positioning value is set for one-third
minimum OA.
2. RA condition is 75
°
F DB and 59.5
°
F WB.
3. OA condition is 40
°
F DB and 35
°
F WB.
4. The MA controller is set at 60
°
F.
5. The desired MA temperature can be maintained until the
OA temperature falls below the temperature at which only
minimum OA is admitted and until the OA is greater
than 60
°
F.
C2545-1
60
°
F DB MA
CONTROLLER SETPOINT
RA 75
°
F DB, 59.5
°
F WB
MA
OA
40
°
F DB, 35
°
F WB
3
2
1
The following results are obtained:
Item
No.
Explanation
1
As OA temperature varies between 30
°
F and
60
°
F, the MA condition lies on the 60
°
F DB
line.
2
As OA temperature rises above 60
°
F DB, 100
percent OA is admitted, and the MA condition
will lie to the right of the 60
°
F DB line.
3
As OA temperatures fall below 30
°
F DB, one-
third OA (set by the manual positioning
switch) is admitted, and the MA condition
will lie to the left of the 60
°
F DB line.
Summary of Contents for AUTOMATIC CONTROL
Page 4: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL iv ...
Page 6: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL vi ...
Page 11: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 1 CONTROL SYSTEMS FUNDMENTALS ...
Page 12: ......
Page 46: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 36 ...
Page 66: ...PSYCHROMETRIC CHART FUNDAMENTALS 56 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 128: ...ENGINEERING MANUAL OF AUTOMATION CONTROL ELECTRIC CONTROL FUNDAMENTALS 118 ...
Page 158: ...MICROPROCESSOR BASED DDC FUNDAMENTALS 148 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 210: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL BUILDING MANAGEMENT SYSTEM FUNDAMENTALS 200 ...
Page 440: ...ENGINEERING MANULA OF AUTOMATIC CONTROL INDIVIDUAL ROOM CONTROL APPLICATIONS 430 ...
Page 516: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 506 Notes ...
Page 517: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 507 Notes ...
Page 518: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 508 ...