ENGINEERING MANUAL OF AUTOMATIC CONTROL
VALVE SELECTION AND SIZING
447
Two-Position Applications
Use line sized valves whenever possible. If the valve size
must be reduced, use:
h = 20% x (Pm-Pr)
Where
Pm = Pressure in supply main in psig or psia (gage
or absolute pressure).
Pr = Pressure in return in psig or psia. A negative
value if a vacuum return.
STEAM VALVE SIZING EXAMPLES
EXAMPLE 1:
A two-way linear valve (V1) is needed to control high-
pressure steam flow to a steam-to-water heat exchanger. An
industrial-type valve is specified. Steam pressure in the
supply main is 80 psig with no superheat, pressure in return
is equal to atmospheric pressure, water flow is 82.5 gpm,
and the water temperature difference is 20F.
Use the steam valve Cv formula to determine capacity
index for Valve V1 as follows:
Where:
Q = The quantity of steam required to pass
through the valve is found using the
converter valve formula:
Q = gpm x TD
w
x 0.49
Where:
gpm = 82.5 gpm water flow through exchanger
TDw = 20F temperature difference
0.49 = A scaling constant
Substituting this data in the formula:
Q = 808.5 pounds per hour
h = The pressure drop across a valve in a
modulating application is:
h = 80% x (Pm – Pr)
Where:
Pm = Upstream pressure in supply main is 80 psig.
Pr = Pressure in return is atmospheric pressure or
0 psig.
Substituting this data in the pressure drop formula:
h = 0.80 x (80 – 0)
= 0.80 x 80
= 64 psi
Average Radiator
of Convector
Temperature,
Deg F
Cast Iron
Radiator
Btu/Hr/EDR a
Convector,
Btu/Hr/EDR b
215
240
240
200
209
205
190
187
183
180
167
162
170
148
140
160
129
120
150
111
102
140
93
85
130
76
69
120
60
53
110
45
39
100
31
27
90
18
16
a
At Room Temperature.
b
At 65F Inlet Air Temperature
STEAM VALVE PRESSURE DROP
Proportional Applications
When specified, use that pressure drop (h) across the valve.
When not specified:
1. Calculate the pressure drop (h) across the valve for good
modulating control:
h = 80% x (Pm – Pr)
NOTE: For a zone valve in a system using radiator orifices
use:
h = (50 to 75)% x (Pm – Pr)
Where
Pm = Pressure in supply main in psig or psia (gage
or absolute pressure).
Pr = Pressure in return in psig or psia. A negative
value if a vacuum return.
2. Determine the critical pressure drop:
hcritical = 50% x Pma
Where:
Pma = Pressure in supply main in psia (absolute
pressure)
psia = psig + 14.7
Use the smaller value h or hcritical when calculating Cv.
Cv =
(1 + 0.00075s)Q V
63.5 h
Table 4. Output of Radiators and Convectors.
Summary of Contents for AUTOMATIC CONTROL
Page 4: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL iv ...
Page 6: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL vi ...
Page 11: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 1 CONTROL SYSTEMS FUNDMENTALS ...
Page 12: ......
Page 46: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 36 ...
Page 66: ...PSYCHROMETRIC CHART FUNDAMENTALS 56 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 128: ...ENGINEERING MANUAL OF AUTOMATION CONTROL ELECTRIC CONTROL FUNDAMENTALS 118 ...
Page 158: ...MICROPROCESSOR BASED DDC FUNDAMENTALS 148 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 210: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL BUILDING MANAGEMENT SYSTEM FUNDAMENTALS 200 ...
Page 440: ...ENGINEERING MANULA OF AUTOMATIC CONTROL INDIVIDUAL ROOM CONTROL APPLICATIONS 430 ...
Page 516: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 506 Notes ...
Page 517: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 507 Notes ...
Page 518: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 508 ...