Gree GMV6 HR DC Inverter VRF Units Service Manual
280
(1) Before the inspection: Find a correct digital multimeter and switch it to the diode gear. Power off the
unit and wait two minutes. Disconnect the U, V and W cables of the fans from the drive board. Do
not operate without waiting two minutes after the unit is powered off.
(2) Testing method: Point the black probe of the multimeter to the P bonding pad shown in the following
figure and the red probe to U, V and W wiring terminals respectively and check the readings of the
multimeter; point the red probe of the multimeter to the N bonding pad shown in the following figure
and the black probe to U, V and W wiring terminal respectively and check the readings of the
multimeter.
(3) Result analysis: If all the readings of the multimeter are between 0.3 V and 0.7 V in the above six
conditions, the module is normal; if any of the readings is 0, the module is damaged.
4.1.10 Main Board
The main board is used to control the load of the ODU.
Summary of Contents for GMVVQ1015WM/C-X
Page 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Page 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Page 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Page 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Page 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Page 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Page 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Page 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Page 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Page 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Page 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Page 433: ...JF00304244...