Gree GMV6 HR DC Inverter VRF Units Service Manual
111
■ The main board operates improperly.
Troubleshooting:
No
Yes
"C2" Communication Fault
Between t he Primary Controller
and Invert er Compressor Driver
Whet her t he communication
cables between the main board of outdoor
unit and inverter compressor drive board
are connected properly?
Connect the communication
cables properly
No
Replace the compressor drive
board
The main cont rol board may be
abnormal
Yes
Replace the main cont rol board
Whet her t he outdoor unit's
compressor drive board is normal?
Yes
2.32 "C3" Communication Fault Between the Primary Controller and
Inverter Fan Driver
Fault display:
main board of outdoor unit, wired controller of indoor unit and receiver of indoor unit
display
Fault diagnosis:
When the outdoor unit fails to detect inverter fan driver for 30 consecutive seconds, the fault is
generated.
Possible causes:
■ The communication cables between the main board of outdoor unit and inverter fan driver inside
the module are connected improperly;
■ The inverter fan driver operates improperly;
■ The main board operates improperly.
Troubleshooting:
Summary of Contents for GMVVQ1015WM/C-X
Page 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Page 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Page 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Page 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Page 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Page 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Page 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Page 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Page 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Page 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Page 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Page 433: ...JF00304244...