Gree GMV6 HR DC Inverter VRF Units Service Manual
188
2.126 "L9" Inconsistent Number of Indoor Units Under Integrated
Control
Fault display:
wired controller of indoor unit and receiver of indoor unit display
Applicable models:
all indoor units
Fault diagnosis:
When more than 16 indoor units are connected to the wired controller or the number of indoor units
connected to the wired controller is not the same as what is configured under integrated control, the fault
is generated.
Possible causes:
■ More than 16 indoor units are connected to one wired controller;
■ The number of indoor units connected to the wired controller is not the same as what is configured
under integrated control.
Troubleshooting:
"L9" Inco nsi stent Number
of Indo or Units Unde r
Inte grated Co ntro l
Whether more th an
16 indo or units are connected to the
wired controller?
Set the wired controller so that
one wired controller can only
control 16 indo or units at most
Yes
Enter th e wire d controlle r p arameter
settings (P14) to set the numbe r of
indo or units unde r in teg rate d control
to b e the same a s th e n umber of
indo or units th at are conne cted to the
wired controller
No
2.127 "LA" Inconsistent Series of Indoor Units Under Integrated
Control
Fault display:
wired controller of indoor unit and receiver of indoor unit display
Applicable models:
all indoor units
Fault diagnosis:
When the wired controller detects that the multiple indoor units connected to it belong to different
series, the fault is generated.
Possible causes:
■ The multiple indoor units connected to the wired controller belong to different series.
Troubleshooting:
Make sure that the multiple indoor units connected to the wired controller belong to the same series.
Summary of Contents for GMVVQ1015WM/C-X
Page 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Page 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Page 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Page 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Page 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Page 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Page 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Page 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Page 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Page 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Page 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Page 433: ...JF00304244...