Gree GMV6 HR DC Inverter VRF Units Service Manual
198
Yes
“o8” IDU drive
communication error
If it is loosened or
there are foreign
objects, retighten it
after treatment
Detecting circuit might
be abnormal
Check the terminal between
external drive board and main control
board to see if it is loose or any
foreign objects inside?
Replace the drive board and
main control board to confirm
and replace the faulted board
No
2.149 “o9” IDU main control communication error
Error display:
ODU main board and IDU wired controller will display
Applicable model:
multi VRF IDU with DC motor
Error judgment condition and method:
If the main control does not receive data in 30 consecutive seconds, it will report communication error; if the
drive does not receive data in 30 consecutive seconds, it will report communication error.
Possible reasons:
■
Poor contact between main control board and drive board communication terminal
■
Detecting circuit is abnormal
Troubleshooting:
Summary of Contents for GMVVQ1015WM/C-X
Page 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Page 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Page 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Page 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Page 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Page 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Page 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Page 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Page 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Page 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Page 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Page 433: ...JF00304244...