Gree GMV6 HR DC Inverter VRF Units Service Manual
162
2.99 "H5" Inverter Fan Over-current Protection
Fault display:
main board of outdoor unit displays
Fault diagnosis:
If the fault code displayed on the 2-digit digital LED of the outdoor unit's main control board is H5, it
indicates the over-current protection for the inverter fan.
Possible causes:
■ Poor contact of fan's UVW cables;
■ The fan is damaged;
■ The blades are stuck (the blades are blocked or the motor shaft gets rusty);
■ The fan drive board operates improperly.
Troubleshooting:
"H5" Inve rte r Fan
Over-current Protection
The fan dr ive boa rd is
abn ormal
Yes
Replace th e fan drive board
No
Whether th e U, V and W p hases of fan
wires a re con nected pro perly?
Yes
No
Replace th e fan
Whether the resistance between
the windings of each phase for the fan is normal
(generally less than 10 ohms)? Whether the resistance values are
equal to each other? Is grounding insulation of the phase
windings of the fan normal (generally greater
than 2 megohms)?
Yes
Yes
Remove forei gn matters
Whether blad es are stuck
due to fore ign ma tters o r ru sting
of motor sh aft?
Yes
Yes
Replace th e faulty fan
Have o the r faults
occurred at the same time (for e xa mpl e,
fan startup fai lure (HJ), IPM modu le p rote ction
(H6) and loss o f synchron iza tion
for fan (H9))?
Summary of Contents for GMVVQ1015WM/C-X
Page 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Page 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Page 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Page 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Page 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Page 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Page 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Page 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Page 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Page 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Page 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Page 433: ...JF00304244...