Gree GMV6 HR DC Inverter VRF Units Service Manual
212
"U4" Refrigerant Loss
Protection
Whether the refrigerant is
added in accordance with the
design requirements?
No
Check and troubleshoot the
leaks of pipes
2.167 "U6" Abnormal Valve Prompt
Fault display:
main board of outdoor unit, wired controller of indoor unit and receiver of indoor unit
display
Fault diagnosis:
During commissioning process, determine whether the check valve of the outdoor unit is open by
detecting the unit's parameters by the pressure sensor. If the parameters are abnormal, the unit prompts
you to confirm whether you want to open the check valve again. After confirmation, press SW4 to
proceed.
Possible causes:
■ The check valve of the outdoor unit is not open.
Troubleshooting: Reconfirm and open the check valve of the outdoor unit.
2.168 "U8" Abnormal Pipes of the Indoor Unit
Fault display:
main board of outdoor unit, wired controller of indoor unit and receiver of indoor unit
display
Fault diagnosis:
During commissioning process, check the temperature of the indoor unit's pipes to determine
whether the pipes are blocked. Any abnormal parameters found would indicate that the unit has the fault.
Possible causes:
■ The electronic expansion valve operates improperly;
■ The indoor unit's pipes are blocked.
Troubleshooting:
Summary of Contents for GMVVQ1015WM/C-X
Page 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Page 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Page 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Page 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Page 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Page 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Page 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Page 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Page 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Page 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Page 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Page 433: ...JF00304244...