Gree GMV6 HR DC Inverter VRF Units Service Manual
27
SW1 up button and SW4 back button are pressed for over 5 seconds, the system enters
non-wired-controller commissioning mode, and no longer detects the communication status between the
wired controller and indoor units.
3.2.2.3 Debugging Through the Main Board of Outdoor Unit
When conducting the debugging through the main board of outdoor unit, the main board has the
following debugging operation functions.
Step 1:
Cover all the front panels of the outdoor unit and open the debugging window of each basic
module.
Step 2:
When the outdoor unit is powered off, set one of the modules as the master module. For the
setting method, see “Master Module DIP Switch Code Setting (SA8_MASTER-S)”.
Step 3:
Under the power-on state of the outdoor unit, set the corresponding static pressure module
for the unit according to the design requirements of the outdoor static pressure of the project.
Step 4:
The module address is displayed as “01” is the master module. On the master module,
press and hold the SW3 confirmation button for 5 seconds or press the SW3 confirmation button for
more than 10 seconds to enter the unit debugging function.
Step 5:
Wait. The unit automatically runs the steps 01 and 02 at this time.
If the master module is set incorrectly in step 01, the following corresponding fault is displayed in
step 01:
—
Debugging
code
Progress code
Status code
Meaning
Progress
LED1
LED2
LED3
Code
Display
status
Code
Display
status
Code
Display
status
01_ set up
master unit
db
ON
01
ON
CC
ON
Mater module hasn’t been set in the system. It
needs to reset it.
db
ON
01
ON
CF
ON
More than two master modules are set in the
system and it needs to reset it.
db
ON
01
ON
OC
ON
Mater module of system has been set
successfully. Enter into the next step
automatically.
According to the above fault phenomenon, reset the master module according to the setting method
of “Master Module DIP Switch Code Setting (SA8_MASTER-S)”, and re-enter into the debugging after
setting.
During the assignment process, all module digital tubes displays are as below:
—
Debugging code
Progress code
Status code
Progress
LED1
LED2
LED3
Code
Display
status
Code
Display
status
Code
Display
status
02_allocate addresses
db
ON
02
ON
Ad
Flash
Step 6:
When the unit is running to step 03, it displays the number of modules connected to the
outdoor connection. At this time, the main board of each module is displayed as below:
Summary of Contents for GMVVQ1015WM/C-X
Page 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Page 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Page 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Page 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Page 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Page 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Page 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Page 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Page 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Page 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Page 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Page 433: ...JF00304244...