Gree GMV6 HR DC Inverter VRF Units Service Manual
371
(4) Remove the side panel assembly without removing the mounting plate of electric
component, side plate sub-assy 1, and side plate sub-assy 2. Please refer to section 5.2.1.4
Remove the Side Plate.
Disassembly steps
(1) Remove the rubber materials such as the insulation sleeve and pipe fixing block near the
electronic expansion valve that need to be replaced;
(2) Unscrew the electronic expansion valve coil to loosen it and then remove it;
(3) Unsolder the connecting pipe of the electronic expansion valve and take out the old
electronic expansion valve;
NOTE: When welding, use a damp cloth to wrap the surrounding electronic expansion valve
and important components.
1- electronic expansion valve coil 2- electronic expansion valve
Installation steps
(1) Install the new electronic expansion valve to a correct position;
(2) Weld the connecting pipe of electronic expansion valve and fill it with nitrogen for
protection during welding (unsolder the connecting pipe of the liquid pipe outside the unit for
nitrogen charging protection);
NOTE: When welding, wrap the valve body with a damp cloth. The electronic expansion valve
and important components near the welding point also need to be wrapped with a damp cloth.
Summary of Contents for GMVVQ1015WM/C-X
Page 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Page 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Page 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Page 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Page 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Page 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Page 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Page 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Page 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Page 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Page 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Page 433: ...JF00304244...