Gree GMV6 HR DC Inverter VRF Units Service Manual
342
3
)
Confirm the compressor oil return pipe.
Remove the compressor oil return pipeline and check the impurities in the pipeline.
CAUTION!
Check the system components that need to be replaced, and ensure that pipe openings of the
damaged components are sealed with tape or the like in time to ensure that they are in good
condition for further analysis.
Collect the amount of compressor oil poured out from the oil separator, gas-liquid separator
and oil equalizer, and make relevant records to facilitate the replacement of compressors,
gas-liquid separator and other components, and adding of lubricant to the system. The total
Summary of Contents for GMVVQ1015WM/C-X
Page 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Page 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Page 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Page 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Page 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Page 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Page 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Page 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Page 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Page 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Page 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Page 433: ...JF00304244...