Gree GMV6 HR DC Inverter VRF Units Service Manual
276
(1) Before the inspection: Find a correct digital multimeter and switch it to the diode gear. Power off
the unit and wait two minutes. Disconnect the U, V and W cables of the compressor and L1, L2
and L3 power cables from the drive board. Do not operate without waiting two minutes after the
unit is powered off.
(2) Testing method:
①
Point the black probe of the multimeter to the P1 bonding pad shown in the following figure
and the red probe to L1, L2 and L3 wiring terminals respectively and check the readings of the
multimeter; point the red probe of the multimeter to the N1 bonding pad shown in the following
figure and the black probe to L1, L2 and L3 wiring terminals respectively and check the
readings of the multimeter.
②
Point the black probe of the multimeter to the P2 bonding pad shown in the following figure
and the red probe to U, V and W wiring terminals respectively and check the readings of the
multimeter; point the red probe of the multimeter to the N2 bonding pad shown in the following
figure and the black probe to U, V and W wiring terminal respectively and check the readings of
the multimeter.
(3) Result analysis: If all the readings of the multimeter are between 0.3 V and 0.7 V in the above
12 conditions, the module is normal; if any of the readings is 0, the module is damaged.
Summary of Contents for GMVVQ1015WM/C-X
Page 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Page 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Page 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Page 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Page 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Page 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Page 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Page 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Page 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Page 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Page 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Page 433: ...JF00304244...