Gree GMV6 HR DC Inverter VRF Units Service Manual
179
2.116 "J8" High Pressure Ratio Protection
Fault display:
main board of outdoor unit, wired controller of indoor unit and receiver of indoor unit
display
Fault diagnosis:
When the ratio between the system high pressure and the low pressure during operation detected
by the pressure sensor exceeds 8, the unit will stop running to ensure safe operation.
Possible causes:
■ The pressure sensor is abnormal;
■ The ambient temperature where the unit operates exceeds the limit.
Troubleshooting:
"J8" Over High Pressu re
Ratio P rote ction
Replace th e p ressur e
sensor
Yes
Whether the air return
te mperature of the unit excee ds the limit during
operation (requirements in cooling mode: outdoor ambient
te mperature -5°C to +50°C, indoor ambient temp erature 16°C to 32°C;
requirements in heating mode: outdoor ambient temperature
-20°C to +24°C, indoor ambient
te mperature 16°C to 30°C)?
Whether th e h igh and low
pressure sensors are op erating prope rly
(based on the Tab le of Characteristics
of P ressur e S ensors)?
No
This case is normal as i t is
subject to ambient
temperature
Yes
Summary of Contents for GMVVQ1015WM/C-X
Page 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Page 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Page 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Page 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Page 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Page 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Page 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Page 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Page 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Page 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Page 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Page 433: ...JF00304244...