Gree GMV6 HR DC Inverter VRF Units Service Manual
354
3 - bolt;
⑧
- blade.
5.1.7 Removing and Installing Condenser
Preparations
(1) Use the power circuit breaker to switch off the power of the GMV6 HR VRF system.
(2) Make sure that the unit pipeline system is free of refrigerant.
(3) Remove the unit’s panel by referring to 5.1.1 Removing and Installing the Unit Panel.
(4) Remove the top cover assembly by referring to 5.1.2 Removing and Installing the Unit
Top Cover Assembly.
Removing procedure
(1) Remove the baffle ring 2 and the fan unit 3 in turn, and the unit is shown as 4 after the
removing.