2.151 "P1" Malfunctioning Compressor Drive Board
Fault display: wired controller of indoor unit displays
Fault diagnosis:
If the fault code displayed on the wired controller of the indoor unit is P1, check the fault code
displayed on the 2-digit digital LED of the main control board of the outdoor unit, based on which you are
able to identify the specific fault of the compressor drive board. Then, troubleshoot the fault according to
the corresponding troubleshooting methods.
Possible causes:
■ Inverter compressor over
-current protection (2-digit digital LED of the main control board of the
outdoor unit displays P5);
■ IPM module protection for the compressor drive (2
-digit digital LED of the main control board of
the outdoor unit displays P6);
■ Communication fault of compressor drive (2
-digit digital LED of the main control board of the
outdoor unit displays C2).
Troubleshooting:
based on the faults displayed on the main board of the outdoor unit.
2.152 "P2" Input Voltage Protection for the Compressor Drive Board
Fault display:
wired controller of indoor unit displays
Fault diagnosis:
If fault code displayed on the wired controller of the indoor unit is P2, check the fault code displayed
on the 2-digit digital LED of the main control board of the outdoor unit, based on which you are able to
identify the specific fault of the compressor drive board. Then, troubleshoot the fault according to the
corresponding troubleshooting methods.
Possible causes:
■ Over voltage protection for the DC bus of compressor drive (2
-digit digital LED of the main control
board of the outdoor unit displays PH);
■ Under voltage protection for the DC bus of compressor drive (2
-digit digital LED of the main
control board of the outdoor unit displays PL).
Troubleshooting:
based on the faults displayed on the main board of the outdoor unit.
2.153 "P3" Reset Protection for the Compressor Drive Module
Fault display:
main board of outdoor unit displays
Fault diagnosis:
If the fault code displayed on the 2-digit digital LED of the outdoor unit's main control board is P3, it
indicates the reset protection for the compressor drive board.
Possible causes:
■ The compressor drive operates improperly
Troubleshooting:
Summary of Contents for GMVVQ1015WM/C-X
Page 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Page 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Page 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Page 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Page 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Page 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Page 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Page 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Page 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Page 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Page 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Page 433: ...JF00304244...