Gree GMV6 HR DC Inverter VRF Units Service Manual
185
2.122 "L4" Supply Power Over-current Protection
Fault display:
wired controller of indoor unit and receiver of indoor unit display
Applicable models:
all indoor units
Fault diagnosis:
When the current supplied to the wired controller by the indoor unit is too large, the fault is
generated.
Possible causes:
■ The wires of
the wired controller are short circuited;
■ The main board of indoor unit operates improperly;
■ The main board of the wired controller is abnormal.
Troubleshooting:
"L4" Sup ply Po wer
Over-current Protection
Whether th e p ower
cord of the wi red con tro ller is
short circuited?
Replace th e wire d controlle r
Yes
No
Reconnect the power co rd of
the wire d con troll er
Yes
No
Is th e main bo ard of the wir ed
controller abn ormal?
The ma in b oard of in door
unit opera tes imp roperly
Replace th e main bo ard of
indo or unit
Yes
Summary of Contents for GMVVQ1015WM/C-X
Page 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Page 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Page 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Page 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Page 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Page 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Page 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Page 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Page 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Page 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Page 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Page 433: ...JF00304244...