Gree GMV6 HR DC Inverter VRF Units Service Manual
118
If two or more master units' DIP switches (SA2) are detected to be master unit's DIP switches in the
network (that is, SA2 DIP switch is "00000"), the fault of multiple master units is reported.
Possible causes:
■ If two or more master units' DIP switches (SA2) are detected to be master unit's DIP switches,
keep only one master unit's DIP switch (SA2) to be "00000" and other master units' DIP switches (SA2)
to be different;
■ Abnormal DIP switch or main board.
Troubleshooting:
Yes
"CJ" System Addre ss Cod e
Conflict
Kee p the SA2 DIP switch to be
"000 00" for o nly on e master u nit, and
set that for oth er ma ster units to b e
diffe rent. Afte r re dialing, power on the
redi aled units aga in
The detection circuit may
ope rate impro perly
Yes
Replace th e main control
boa rd
No
Whether two or more master units'
DIP switches (SA2) are set to the master
unit's DIP switche s?
Summary of Contents for GMVVQ1015WM/C-X
Page 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Page 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Page 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Page 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Page 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Page 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Page 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Page 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Page 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Page 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Page 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Page 433: ...JF00304244...