4.1.6.1 Mechanical Inspection
Step 1:
Switch off the power of the ODU.
Step 2:
Check whether the connector between the fan motor and fan drive board is firmly
connected.
Step 3:
Rotate the blades with a hand to check whether they can rotate smoothly and whether the
blades rub the baffle ring during rotation. If the blades are blocked during rotation, the motor needs to be
replaced; if the blades rub the baffle ring during rotation, check whether the blades and baffle ring deform
and needs to be replaced.
4.1.6.2 Electrical Inspection
Switch off the power of the ODU. Disconnect the connector between the fan motor and fan drive
board. Use a multimeter to measure the resistance of each contact point of the motor terminal. The
normal range of the resistance is shown in the following table. If any value is beyond the normal range,
the motor is damaged and needs to be replaced.
Terminal layout
Diagram of internal coils
Range of coil
resistance between
any two phases
3.W Blue
1.U Brown
2.V Black
U (BN brown)
V (BK black)
W (BU blue)
10.2Ω±7%
4.1.7 Compressor
Specifications
Description
Models: AA55PHDG-D1Y2, DA80PHDG-D1Y2
Compression refrigerant, recycling refrigerant.
Summary of Contents for GMVVQ1015WM/C-X
Page 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Page 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Page 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Page 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Page 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Page 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Page 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Page 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Page 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Page 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Page 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Page 433: ...JF00304244...