Gree GMV6 HR DC Inverter VRF Units Service Manual
68
14
Under voltage protection for the DC bus of
inverter compressor driver
33
Inverter outdoor fan over-current protection.
15
Over voltage protection for DC bus of the inverter
compressor driver.
34
Current detection circuit fault of the inverter
outdoor fan driver.
16
IPM module protection for the inverter
compressor driver.
35
Loss of synchronization protection for the inverter
outdoor fan.
17
Inverter compressor startup failure
36
Communication fault between the primary
controller and inverter outdoor fan driver.
18
Inverter compressor phase loss protection.
37
Over temperature protection for the inverter
outdoor fan driver module.
19
Inverter compressor driver module reset.
38
Temperature sensor fault of the inverter outdoor
fan driver module.
The figure below shows the
Debug
page.
LED1
LED2
LED3
Function Code
Display status
Sequence
Display status
Current status
Display status
n6
On
01
On
Historical fault/module
address
Alternated
n6
On
02
On
Alternated
n6
On
03
On
Alternated
n6
On
04
On
Alternated
n6
On
05
On
Alternated
If historical faults are less than five, after the last fault is displayed, LED2 and LED3 display 00,
indicating no more fault.
In fault query status, press and hold the SW3 confirm button for over 5 seconds to clear all historical
faults of the outdoor unit.
4.1.2.4.2 n7 Parameter Query
Press the SW1 up button and the SW2 down button to select parameter query. The master unit
displays as follows:
LED1
LED2
LED3
Function Code
Display status
Current process/mode
Display status
Current status
Display status
n7
Blinks
00
Blinks
00
Blinks
Press the SW3 confirm button on the master unit to confirm the selection.
Introduction:
This function is used to query running parameters of each module of the outdoor unit in real time.
Operations:
In parameter query status, the master unit displays as follows:
LED1
LED2
LED3
Function Code
Display status
Module address
Display status
Current status
Display status
n7
On
01
Blinks
00
Blinks
n7
On
02
Blinks
00
Blinks
n7
On
03
Blinks
00
Blinks
n7
On
04
Blinks
00
Blinks
Press the SW1 up button and the SW2 down button to select the corresponding query module, and
press the SW3 confirm button. The unit displays as follows:
LED1
LED2
LED3
Function Code
Display status
Parameter code
Display status
Current status
Display status
n7
On
XX
On
Value
Blinks
LED2 displays the module parameter code, and LED3 displays the specific value. The parameters
Summary of Contents for GMVVQ1015WM/C-X
Page 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Page 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Page 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Page 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Page 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Page 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Page 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Page 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Page 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Page 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Page 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Page 433: ...JF00304244...