Re-engineer the unit to increase indoor unit capacity or decrease outdoor unit capacity.
2.41 "CC" No Master Units Fault
Fault display:
main board of outdoor unit, wired controller of indoor unit and receiver of indoor unit
display
Fault diagnosis:
The main board detects the master DIP switch (SA8) and determines whether it is the master.
When no master unit is detected in the multi-module communication network, the fault is generated.
Possible causes:
■ The master DIP switch is abnormal and no master unit exists in the network;
■ The communication cables are abnormal, causing the master unit to be disconnected;
■ Abnormal detection circuit.
Troubleshooting:
No
Yes
"CC" No Master Un its Fau lt
Make sure that o nly one maste r
unit exi sts in the networ k. Afte r
redi aling, power on the rediale d
module s agai n
No
Pro perly conn ect the
commu nicatio n cable an d make
sure th at it is in the same
network with o the r modu les
The ma in con trol boa rd
may be ab normal
Yes
Replace th e main control
boa rd
Yes
Whether DIP switch is
dial ed properl y fo r the master unit (SA8)
among all the mo dules
in th e n etwork?
Whether th e
commu nicatio n cable s
for the module s of the master unit by
dial ing are co nnecte d
prop erly ?
2.42
“
CE” Mode exchanger and IDU communication error
Error display:
mode exchanger main board will display
Applicable model:
all mode exchangers
Error judgment condition and method:
For the mode exchanger, no IDU communication is detected in 1 consecutive minute.
Possible reasons:
■
Poor contact between mode exchanger main control board and IDU main control board terminal
■
Communication cord is abnormal
■
Circuit is abnormal
Troubleshooting:
Summary of Contents for GMVVQ1015WM/C-X
Page 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Page 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Page 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Page 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Page 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Page 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Page 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Page 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Page 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Page 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Page 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Page 433: ...JF00304244...