Gree GMV6 HR DC Inverter VRF Units Service Manual
49
LED1
LED2
LED3
Function Name
Function
code
Display
status
Current
process
Display
status
Current
status
Display
status
A7
On
00
Blinks
00
Blinks
Outdoor unit silence
A6
On
00
Blinks
00
Blinks
Cooling/heating of the entire
system
A2
On
00
Blinks
00
Blinks
Refrigerant recycle
A8
On
00
Blinks
00
Blinks
After-sales vacuum pumping
n0
On
01
Blinks
00
Blinks
Auto energy saving
n3
On
00
Blinks
00
Blinks
Forced defrosting
n4
On
00
Blinks
00
Blinks
Forced energy saving
n5
On
00
Blinks
00
Blinks
Indoor unit engineering SN
offset
qJ
On
00
Blinks
00
Blinks
One-button drainage
C8
On
00
Blinks
00
Blinks
Compressor emergency setting
CA
On
00
Blinks
00
Blinks
Module emergency setting
C9
On
00
Blinks
00
Blinks
Fan emergency setting
4J
On
00
Blinks
00
Blinks
Components and parts
emergency setting
1C
On
00
Blinks
00
Blinks
Continuous heating
1F
On
00
Blinks
00
Blinks
SRL low-pressure control
1G
On
00
Blinks
00
Blinks
Outdoor static pressure setting
1H
On
00
Blinks
00
Blinks
Efficient module rotation
4n
On
00
Blinks
00
Blinks
Adaptive control of noise
4q
On
00
Blinks
00
Blinks
Forced switch of the electric
heater of an indoor unit
5L
On
00
Blinks
00
Blinks
Fan reverse dust removal
5n
On
00
Blinks
00
Blinks
Fan anti-snow
Then, set the function/parameter accordingly.
After entering the function/parameter setting status, press the SW4 back button to return to the previous
process or exit the function setting status. If you do not press any button in 5 minutes, the system will
automatically exit the current screen and the unit will resume displaying the current status.
4.1.2.3.1 "A2" Refrigerant Recycle
Introduction:
This function is mainly used to recycle some refrigerant in the faulty module or the indoor unit
pipeline during unit maintenance. The table below lists the maximum amount of refrigerant that can be
recycled:
Basic Module Model
Maximum Amount of Refrigerant to Be Recycled
GMV-VQ224WM/C-X
6.0
GMV-VQ280WM/C-X
6.0
GMV-VQ335WM/C-X
9.0
GMV-VQ400WM/C-X
8.5
GMV-VQ450WM/C-X
8.5
GMV-VQ504WM/C-X
13.0
GMV-VQ560WM/C-X
13.0
GMV-VQ615WM/C-X
13.0
Refrigerant recycle can be divided to two modes: fault module refrigerant recycle and indoor unit
Summary of Contents for GMVVQ1015WM/C-X
Page 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Page 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Page 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Page 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Page 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Page 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Page 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Page 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Page 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Page 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Page 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Page 433: ...JF00304244...