Step 6: Discharging refrigerant
The refrigerant in the system needs to be discharged from the high and low pressure sides of
the system concurrently. If the refrigerant is discharged from one side only, the sealed scroll will
hinder the refrigerant from being fully discharged. Do not discharge the refrigerant too fast (in no
shorter than 12h). Otherwise, a large amount of lubricant will be discharged together with the
refrigerant as well.
Step 7: Removing compressors
(
1
)
Remove the fixing nut, gasket and damping washer of compressor.
1
—
nut 2
—
gasket 3
—
damping washer
(
2
)
Weld the welding point for nozzle
A. Applicable model: GMV-VQ224/280/335/400/450WM/C-X
Summary of Contents for GMVVQ1015WM/C-X
Page 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Page 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Page 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Page 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Page 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Page 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Page 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Page 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Page 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Page 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Page 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Page 433: ...JF00304244...