Gree GMV6 HR DC Inverter VRF Units Service Manual
338
circuit of the unit are normal, only the compressor needs to be replaced.
The procedure of checking oil quality is described as follows:
①
After removing a compressor, shake the compressor on a solid ground in the sway
angle of 30 to 45 degrees to ensure that the pollutants deposited on the bottom of the
compressor can be poured out.
Remove the compressor
and shake it on solid
ground anticlockwise
30-45°
②
Place the compressor at a position above the level of the ground, pour oil from the
compressor exhaust port, and use a beverage bottle or other transparent container (with a
volume of over 150 ml) to store oil.
Note that the angle between the axial position of the compressor and the horizontal plane
should not exceed 20 degrees to prevent the compressor from falling and injuring people.
No more than 20°
between the
compressor and
ground
Place a transparent container with
a capacity of above 150ml beneath
the discharge pipe when draining
the lubricant of the compressor to
check the oil quality
③
Place the collected compressor oil in a bright place to check if it contains impurities
and discolors, and smell the compressor oil. Normal lubricant has no obvious pungent odor.
Summary of Contents for GMVVQ1015WM/C-X
Page 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Page 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Page 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Page 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Page 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Page 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Page 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Page 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Page 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Page 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Page 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Page 433: ...JF00304244...