Gree GMV6 HR DC Inverter VRF Units Service Manual
55
LED1
LED2
LED3
Function code
Display status
Current
process/mode
Display status
Current status
Display status
n0
On
01
Blinks
OC
Blinks
n0
On
02
Blinks
OC
Blinks
Step 3:
After selecting the mode, press the SW3 confirm button. The master unit displays as
follows:
LED1
LED2
LED3
Function code
Display status
Current
process/mode
Display status
Current status
Display status
n0
On
01
On
OC
On
n0
On
02
On
OC
On
If you do not press any button on the master unit in 5 minutes, the system will automatically exit the
current screen and the unit will resume displaying the current status. (During setting, press SW4 to
return to the previous process. If the setting is completed, press SW4 to resume the unit to the current
normal working status.)
4.1.2.3.6 n3 Forced Defrosting
Introduction:
This function is used when forced defrosting is required during unit maintenance. After entering
forced defrosting, the system automatically exits according to the exit conditions, and then automatically
runs according to the system conditions.
Setting steps:
Step 1:
Enter n3 forced defrosting, and ensure that the master unit displays as follows:
LED1
LED2
LED3
Function code
Display status
Current
process/mode
Display status
Current status
Display status
n3
On
00
Blinks
00
Blinks
Step 2:
Press the SW3 confirm button. The master module displays as follows:
LED1
LED2
LED3
Function code
Display status
Current
process/mode
Display status
Current status
Display status
n3
On
00
On
00
On
If the defrosting condition is not met, the module displays the set mode. If the setting is completed,
press SW4 to resume the unit to the current normal working status.
When the defrosting exit condition is met, the system automatically exits and resumes normal
running control.
4.1.2.3.7 n4 Forced Energy Saving Mode
Introduction:
The maximum output capability limit is used in scenarios where the user needs to forcibly limit the
system power consumption. Available functions are as follows:
Code
Maximum Output Capability
Summary of Contents for GMVVQ1015WM/C-X
Page 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Page 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Page 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Page 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Page 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Page 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Page 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Page 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Page 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Page 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Page 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Page 433: ...JF00304244...