Gree GMV6 HR DC Inverter VRF Units Service Manual
199
Yes
“o9” IDU main control
communication error
If it is loosened or there
are foreign objects,
retighten it after treatment
Detecting circuit might be abnormal
否
Check the terminal between main
board and external drive board to see if it is
loose or any foreign objects inside?
Replace the main control board
and drive board in turn, then
replace it after confirming the
faulted board.
No
2.150 "P0" Compressor Drive Board Fault
Fault display:
wired controller of indoor unit displays
Fault diagnosis:
If the fault code displayed on the wired controller of the indoor unit is PO, check
the fault code displayed on the 2-digit digital LED of the main control board of the outdoor unit, based on
which you are able to identify the specific fault of the compressor drive board. Then, troubleshoot the
fault according to the corresponding troubleshooting methods.
Possible causes:
■ Compressor drive module reset protection (2
-digit digital LED of the main control board of the
outdoor unit displays P3);
■ Temperature sensor fault of compressor drive (2
-digit digital LED of the main control board of the
outdoor unit displays P7);
■ IP
M over temperature protection for the compressor drive (2-digit digital LED of the main control
board of the outdoor unit displays P8);
■ Current detection circuit fault of compressor drive (2
-digit digital LED of the main control board of
the outdoor unit displays PC);
■ Charging loop fault of compressor drive (2
-digit digital LED of the main control board of the
outdoor unit displays PF);
■ Loss of synchronization protection for the inverter compressor (2
-digit digital LED of the main
control board of the outdoor unit displays P9);
■ Inverter compressor startup failure (2
-digit digital LED of the main control board of the outdoor unit
displays PJ).
Troubleshooting:
based on the faults displayed on the main board of the outdoor unit.
Summary of Contents for GMVVQ1015WM/C-X
Page 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Page 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Page 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Page 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Page 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Page 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Page 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Page 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Page 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Page 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Page 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Page 433: ...JF00304244...