Gree GMV6 HR DC Inverter VRF Units Service Manual
347
amount of lubricant poured out from removing components such as compressors and gas-liquid
separator. If there is obvious abnormality, for example, when the amount of lubricant poured out is
too little or too much, empty the lubricant in the system, and then check the section 3 basic
parameters of the unit in Chapter 1 to determine the amount of lubricant that needs to be
recharged.
The specific amount of additional lubricant is divided into two parts: in the first part, the
compressor lubricant is added according to the number of compressors to be replaced. 1.5L of
lubricant is required for each compressor to be replaced. After replacing the compressors and
other parts such as the gas-liquid separator and filters, use high-pressure nitrogen to clean the
pipelines and recharge the second part of the lubricant according to the lubricant parameters in
the section 3 of Chapter 1.
For example:
①
One compressor needs to be replaced for GMV-VQ450WM/C-X and 1L of lubricant
is discharged from the gas-liquid separator and 0.7L is discharged from the oil separator for
cleaning the system. Therefore, 3.2L (1.5L+1L+0.7L) of lubricant needs to be recharged.
②
One compressor needs to be replaced for GMV-VQ280WM/C-X. The gas-liquid
separator and other parts such as filters need to be replaced. The pipelines need to be
cleaned by high-pressure nitrogen. Nearly all the parts are involved and nearly all the
lubricant is discharged except for a small amount remaining in the pipelines. Therefore, 3.5L
of refrigeration oil needs to be recharged according to the parameter form.
Lubricant recharging method:
1) Only FV68H refrigeration oil can be used for the unit. Verify the model number before
recharging. It is forbidden to use the refrigeration oil of a different model number.
2) Connect the gas and liquid valves of the unit and vacuum the unit for over 30
minutes.
3) Connect a rubber tube to the oil charging valve, open the container containing the
lubricant, discharge the lubricant into the measuring cup and measure the appropriate
recharging amount. If the measuring cup capacity is sufficient to measure the appropriate
lubricant quantity once, the lubricant can be recharged in several times. Record the amount of
lubricant recharged each time, then dip the other end of the rubber tube into the lubricant in
the measuring cup.
4) Vacuum the unit and open the oil charging valve at the same time to charge the
lubricant into the low-pressure side of the unit by using the atmosphere pressure.
5) When the lubricant needs to be recharged several times, close the oil valve before
measuring the lubricant to be recharged. Keep vacuuming the unit during the process.
6) After the appropriate amount of lubricant is recharged, close and seal the oil
charging valve.
Summary of Contents for GMVVQ1015WM/C-X
Page 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Page 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Page 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Page 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Page 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Page 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Page 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Page 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Page 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Page 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Page 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Page 433: ...JF00304244...