Gree GMV6 HR DC Inverter VRF Units Service Manual
61
If you do not press any button in 5 minutes, the system will automatically exit the current screen and
the unit will resume displaying the current status.
If a basic module sets compressor failure emergency operation, the status indicators and LEDs on
the module indicate the corresponding status.
LED1
LED2
LED3
Description
Module address
Module
failure/indoor unit
failure
Module status
ADD
C9
ON
System running-fan emergency operation
status
ADD
C9
OF
System standby-fan emergency operation
status
NOTES!
①
This function is applicable only to dual-fan models;
②
A module can set only one fan to emergency mode;
③
The default status is 00.
④
The system cannot run continuously for more than 120 hours in fan emergency operation
status. If it exceeds 120 hours, the entire system is stopped, and the indoor unit displays
the "Ad" limit operation code.
4.1.2.3.13 CA Module Failure Emergency Operation
This function is after-sales emergency setting when a module works abnormally. It shields the
abnormal module in a short time to ensure the emergency operation of other modules.
Setting steps:
Enter the function setting on the main board of the faulty basic module. The module displays as
follows:
LED1
LED2
LED3
Function code
Display status
Current process
Display status
Current status
Display status
CA
On
00
Blinks
OC
Blinks
Press the SW1 up button and the SW2 down button to select the corresponding module to enter and
exit emergency operation status.
LED1
LED2
LED3
Description
Function
code
Display
status
Current
process
Display
status
Current
status
Display
status
CA
On
00
Blinks
OC
Blinks
All basic modules run normally.
CA
On
01
Blinks
OC
Blinks
The operation of module 1 is
shielded.
CA
On
02
Blinks
OC
Blinks
The operation of module 2 is
shielded.
CA
On
03
Blinks
OC
Blinks
The operation of module 3 is
shielded.
CA
On
04
Blinks
OC
Blinks
The operation of module 4 is
shielded.
After selecting the corresponding value, press the SW3 confirm button. The shielded module
displays as follows:
Summary of Contents for GMVVQ1015WM/C-X
Page 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Page 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Page 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Page 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Page 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Page 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Page 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Page 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Page 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Page 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Page 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Page 433: ...JF00304244...