Gree GMV6 HR DC Inverter VRF Units Service Manual
39
In step "13 Refrigerant charging running" is divided into trial running in manual charging cooling
mode or manual charging heating mode. The system automatically determines and enables indoor unit
cooling or forcibly enables indoor unit heating. When the system runs for 60 minutes without exception, it
determines that the refrigerant is normal, the unit is shut down, and the commissioning is completed.
Alternatively, after staying for 65 minutes in the process, the commissioning is exited and completed.
The interface after the commissioning is shown below. "Debugging completed" indicates that the
commissioning is completed, and the system enters normal standby status 5 seconds later. Step "13
Refrigerant charging running" is reserved.
Summary of Contents for GMVVQ1015WM/C-X
Page 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Page 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Page 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Page 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Page 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Page 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Page 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Page 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Page 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Page 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Page 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Page 433: ...JF00304244...