Gree GMV6 HR DC Inverter VRF Units Service Manual
4
1.4 Water Tank
Model
Product Code
Power Supply
Appearance
SXTVD300LCJ2/A-K
ER20000350
230V~ 50Hz
2 Parameters
2.1 Parameters of Outdoor Unit
2.1.1 Parameters of Basic Modules
Model
-
GMV-VQ224WM/C-X
GMV-VQ280WM/C-X
GMV-VQ335WM/C-X
GMV-VQ400WM/C-X
HP
HP
8
10
12
14
Product Code
-
CN851W3140
CN851W2950
CN851W2370
CN851W3160
Cooling
capacity
Rated
kW
22.4
28
33.5
40
Heating
capacity
Rated
kW
16.2
16.2
18.5
23.5
Max.
kW
25
31.5
37.5
45
Outdoor static pressure
Pa
0-110
0-110
0-110
0-110
Sound pressure level(Cooling) dB(A)
60
61
63
63
Sound power
level(Cooling)
ducted
dB(A)
80
83
83
91
cassette
dB(A)
80
85
86
87
Power Supply
-
380-415V 3N~
50/60Hz
380-415V 3N~
50/60Hz
380-415V 3N~
50/60Hz
380-415V 3N~
50/60Hz
Rated power input
kW
12.87
13.15
13.50
21.0
Rated current
A
23.0
23.5
24.1
37.5
Compressor type
-
Inverter scroll
Inverter scroll
Inverter scroll
Inverter scroll
Compressor quantity
N
1
1
1
1
Refrigeration oil No. of
compressor
-
FV68H
FV68H
FV68H
FV68H
Refrigeration
oil charge
Gross
L
4.6
4.6
4.6
6.1
Compressor
charge
L
1.1
1.1
1.1
1.1
The others
L
3.5
3.5
3.5
5
Refrigerant type
-
R410A
R410A
R410A
R410A
Refrigerant charge
kg
8.2
8.5
9.6
11.1
Maximum drive IDU NO.
unit
13
16
19
23
High pressure gas pipe
mm
Φ15.9
Φ19.05
Φ19.05
Φ22.2
Low pressure gas pipe
mm
Φ19.05
Φ22.2
Φ25.4
Φ25.4
Liquid pipe
mm
Φ9.52
Φ9.52
Φ12.7
Φ12.7
Outline dimensions(W × D ×
H)
mm
930×775×1690
930×775×1690
930×775×1690
1340×775×1690
Packing dimensions (W × D ×
H)
mm
1000×830×1855
1000×830×1855
1000×830×1855
1400×830×1855
Net weight
kg
243
243
256
325
Gross weight
kg
253
253
266
340
Summary of Contents for GMVVQ1015WM/C-X
Page 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Page 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Page 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Page 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Page 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Page 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Page 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Page 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Page 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Page 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Page 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Page 433: ...JF00304244...