Gree GMV6 HR DC Inverter VRF Units Service Manual
190
Yes
“LL” waterflow
switch error
If it is loosened or there
are foreign objects,
retighten it after treatment
Detecting circuit might
be abnormal
Yes
Replace the main
control board
No
Replace the water flow switch
of generator directly
Is the terminal between
Mainboard and water flow switch loose
or any foreign objects inside?
Supplement water again for
the generator waterway
when unblocking the
generator waterway
Is there circulating water in the
circulated waterway of generator?
No
No
Yes
2.131 “LF” Shunt valve setting error
Error display:
wired controller of hydro box will display
Applicable model:
hydro box
Error judgment condition and method:
When setting the corresponding relationship for the floor heating shunt valve and IDU, the generator shall
detect and judge the project code of IDU to see if the nonexistent project code is set or shunt valve setting error
alarm occurs if the same shunt valve is matching with several IDUs (project code)
Possible reasons
■
IDU linked with floor heating is offline
■
Project code conflict or IP conflict
Troubleshooting
Step 1: check if the IDU corresponding to the shunt valve is offline, if yes, the IDU is deemed offline;
Step 2: check if the project code or IP is conflict, if yes, adjust the relationship between shunt valve and IDU
again, allow several shunt valves to match with the same IDU (project code), but never allow the same shunt
valve to match with several IDUs (project code).
2.132 “LU” Inconsistent IDU branch connecting to the wired
controller which controls multiple indoor units of heat recovery
system
Error display:
wired controller will display
Summary of Contents for GMVVQ1015WM/C-X
Page 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Page 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Page 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Page 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Page 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Page 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Page 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Page 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Page 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Page 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Page 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Page 433: ...JF00304244...