Gree GMV6 HR DC Inverter VRF Units Service Manual
5
Model
-
GMV-VQ450WM/C-
X
GMV-VQ504WM/C-X
GMV-VQ560WM/C-
X
GMV-VQ615WM/C-X
HP
HP
16
18
20
22
Product Code
-
CN851W2850
CN851W2380
CN851W3150
CN851W2470
Cooling
capacity
Rated
kW
45.00
50.40
56.00
61.50
Heating
capacity
Rated
kW
23.5
31.00
31.00
33.00
Max.
kW
50.00
56.50
63.00
69.00
Outdoor static pressure
Pa
0-110
0-110
0-110
0-110
Sound pressure
level(Cooling)
dB(A)
63
63
63
64
Sound power
level(Cooling)
ducted
dB(A)
91
89
89
89
cassette
dB(A)
94
87
89
94
Power Supply
-
380-415V 3N~
50/60Hz
380-415V 3N~
50/60Hz
380-415V 3N~
50/60Hz
380-415V 3N~
50/60Hz
Rated power input
kW
22
26.3
26.85
27.41
Rated current
A
39.3
47
48
49
Compressor type
-
Inverter scroll
Inverter scroll
Inverter scroll
Inverter scroll
Compressor quantity
N
1
2
2
2
Refrigeration oil No. of
compressor
-
FV68H
FV68H
FV68H
FV68H
Refrigeration
oil charge
Gross
L
6.1
7.2
7.2
7.2
Compress
or charge
L
1.1
1.1×2
1.1×2
1.1×2
The
others
L
5
5
5
5
Refrigerant type
-
R410A
R410A
R410A
R410A
Refrigerant charge
kg
11.6
12.8
12.8
13.3
Maximum drive IDU NO.
unit
26
29
33
36
High pressure gas pipe
mm
Φ22.2
Φ25.4
Φ25.4
Φ25.4
Low pressure gas pipe
mm
Φ28.6
Φ28.6
Φ28.6
Φ28.6
Liquid pipe
mm
Φ12.7
Φ15.9
Φ15.9
Φ15.9
Outline dimensions(W × D ×
H)
mm
1340×775×1690
1340×775×1690
1340×775×1690
1340×775×1690
Packing dimensions (W × D
× H)
mm
1400×830×1855
1400×830×1855
1400×830×1855
1400×830×1855
Net weight
kg
325
385
385
385
Gross weight
kg
340
400
400
400
Note:
①
Rated cooling capacity test conditions: indoor 27
℃
DB/19
℃
WB, outdoor 35
℃
DB; without
height drop between units.
②
Rated heating capacity test conditions(Tdesingnh): indoor 20
℃
DB, outdoor -10
℃
DB/-11
℃
WB; without height drop between units. Max heating capacity test conditions: indoor 20
℃
DB,
outdoor 7
℃
DB/6
℃
WB; without height drop between units.
③
The total capacity of connected indoor units must be in the range of 50%~135% of the outdoor
unit capacity. The relevant parameters can be corrected by referring to the unit capacity
correction table.
④
The above parameters are tested based on the standard connection pipe length. In the actual
project, the parameters should be corrected referring to the capacity correction for the long
connection pipe of units.
Specifications may be changed due to product improvement. Please refer to nameplates of the units.
Summary of Contents for GMVVQ1015WM/C-X
Page 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Page 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Page 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Page 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Page 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Page 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Page 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Page 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Page 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Page 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Page 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Page 433: ...JF00304244...