Gree GMV6 HR DC Inverter VRF Units Service Manual
210
2.163 "U0" Insufficient Warm-up Time for Compressor
Fault display:
main board of outdoor unit, wired controller of indoor unit and receiver of indoor unit
display
Fault diagnosis:
When the oil preheating period of time before compressor starts is less than eight hours, the unit
generates a fault.
Possible causes:
--
Troubleshooting:
Warm up the whole unit for more than eight hours before startup.
2.164 "U2" Incorrect Settings of Outdoor Unit Capacity DIP
Switch/Jumper Cap
Fault display:
main board of outdoor unit, wired controller of indoor unit and receiver of indoor unit
display
Applicable models:
all outdoor units
Fault diagnosis:
When the capacity DIP switch detected by the outdoor unit's main board is inconsistent with the
unit's actual capacity, or the jumper cap value detected by the outdoor unit's main board is inconsistent
with the actual unit, the fault is generated.
Possible causes:
■ Capacity DIP switch error or jumper cap error (for some models without jumper caps, jumper cap
error is not detected)
■ DIP switch or jumper cap is broken
■ Abnormal detection circuit
Troubleshooting:
"U2" Inco rrect Settings of
Outdoo r Unit Cap aci ty DIP
Switch/Jumper Ca p
The detection circuit may
ope rate impro perly
Yes
Whether capacity DIP switch
on the ma in b oard and jumper cap are
consistent with th e a ctual units?
No
Replace th e main control
boa rd
No
Afte r the unit is powered
off, dial the DIP switch
aga in o r re place the jumpe r
cap and th en power on the
unit again
Summary of Contents for GMVVQ1015WM/C-X
Page 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Page 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Page 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Page 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Page 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Page 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Page 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Page 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Page 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Page 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Page 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Page 433: ...JF00304244...