Gree GMV6 HR DC Inverter VRF Units Service Manual
340
(
3
)
Remove the fixing bolt, take away the gas-liquid separator.
①
. Remove 4 fixing bolts (applicable to model GMV-VQ224/280/335WM/C-X).
②
. Remove 3 fixing bolts (applicable to model GMV-VQ400/450/504/560/615WM/C-X).
Warning!
①
. Safety protection must be done during welding.
②
. After unsoldering the welding point, separate the pipe nozzle and the gas-liquid
separator nozzle for ten seconds to prevent the two nozzles from sticking together. After taking out
the gas-liquid separator, check whether there are impurities and other substances in the gas-liquid
separator. For the checking process, please refer to the compressor oil quality confirmation.
Summary of Contents for GMVVQ1015WM/C-X
Page 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Page 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Page 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Page 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Page 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Page 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Page 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Page 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Page 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Page 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Page 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Page 433: ...JF00304244...