2.2.3 Installation Orientation
Install the servo drive perpendicular to the wall as shown in the figure. The servo drive must be oriented this way
because it is designed to be cooled by natural convection or a cooling fan if required. Firmly secure the servo drive
through two mounting holes.
2.2.4 Installation Method
When installing multiple servo drives side by side in a control panel, observe the following installation method.
Colling Fan
Colling Fan
■
Installation Orientation
Install servo drive perpendicular to the wall so that the front panel (containing connectors) faces outward.
■
Cooling
Provide sufficient space around each servo drive to allow cooling by natural convection or fans.
■
Installing side by side
When installing servo drives side by side, provide at least 10mm space between each individual servo drive and at
least 50mm space above and below each one as well as shown in the figure above. Ensure the temperature inside the
control panel is evenly distributed, and prevent the temperature around each servo drive from increasing excessively.
Cooling Fan
Cooling Fan