Option
Description
Enabled (On) The preset is available for use. You can select it to run a batch.
Disabled (Off) The preset is not available for use. You cannot select it to run a batch. You can always
enable it at a later time.
Preset 1 is always enabled and cannot be disabled.
7. Optional: For two-stage batching, set
% Target
or
Quantity
for the following parameters:
Two-stage batching is a batch that is run on a gas and liquid mixture flowing through a pipeline.
% Target
The values for
Open Primary
,
Open Secondary
,
Close Primary
, and
End
Warning
are each configured as a percent of target.
Quantity
The values for
Open Primary
and
Open Secondary
are each configured as
a quantity at which the valve should open. The values for
Close Primary
and
End Warning
are each configured as a quantity that is subtracted
from the target.
Parameter
Description
End Warning
The % target or quantity level that must be reached to alert the operator
that a batch is ending.
Open Primary
The % target or quantity level that must be reached to open the primary
valve.
Open Secondary
The % target or quantity level that must be reached to open the secondary
valve.
Close Primary
The % target or quantity level that must be reached to close the primary
valve. When configuring by quantity, the amount is referenced to the end
of the batch and not to the beginning of the batch.
Configure batch presets using the Field Communicator
A batch preset is a predefined group of batching parameters. You can define and save up to six batch presets.
When you run a batch, you must choose a preset. You can modify the batch target before you run the batch.
All other settings are fixed.
Procedure
1. Choose
Configure
>
Manual Setup
>
Inputs/Outputs
>
Batcher
>
Setup Presets
.
2. Select the preset that you want to configure.
3. Enable or disable the preset as desired.
Option
Description
Enabled (On) The preset is available for use. You can select it to run a batch.
Disabled (Off) The preset is not available for use. You cannot select it to run a batch. You can always
enable it at a later time.
Configuration and Use Manual
Configure process measurement applications
MMI-20025166
March 2019
Configuration and Use Manual
97