controls the behavior of the mA Output if the transmitter detects a fault condition.
Important
•
The fault action is implemented only if
Alert Severity
is set to Failure. If
Alert Severity
is set to any other
option, the fault action is not implemented.
•
For some faults only: If
Fault Timeout
is set to a non-zero value, the transmitter will not implement the
fault action until the timeout has elapsed.
Procedure
1. Set
mA Output Fault Action
as desired.
•
Default: Downscale
Important
If you set
mA Output Fault Action
to None, the mA Output will be controlled by the setting of
Process
Variable Fault Action
. In most cases, if you set
mA Output Fault Action
to None, you should also set
Process Variable Fault Action
to None.
2. If you set
mA Output Fault Action
to
Upscale
or
Downscale
, set
mA Output Fault Level
to the signal
that the mA Output will produce during a fault.
Related information
Configure Process Variable Fault Action
Interaction between Process Variable Fault Action and other fault actions
Options for mAO Fault Action and mAO Fault Level
Option
mA Output behavior
mA Output Fault Level
Upscale
Goes to the configured fault level
Default: 22.0 mA
Range: 21.0 to 23.0 mA
Downscale (default)
Goes to the configured fault level
Default: 2.0 mA
Range: 1.0 to 3.6 mA
Internal Zero
Goes to the mA Output level associated with a
process variable value of 0 (zero), as determined
by
Lower Range Value
and
Upper Range Value
settings
Not applicable
None
Determined by the setting of
Process Variable
Fault Action
Not applicable
Integrate the meter with the control system
Configuration and Use Manual
March 2019
MMI-20025166
146
Micro Motion Model 5700 Transmitters with Configurable Outputs