Compensation Off
The transmitter sends the close command when the measured batch total reaches
the configured target.
Fixed
Compensation
Value
The transmitter sends the close command when the measured batch total equals the
target minus the value configured for
Fixed Overshoot Compensation
. This value is
configured in the current mass or volume unit, and applies to all presets.
AOC Algorithm
The transmitter compares the actual measured amount of each batch to the batch
target, and determines the adjustment by calibrating itself according to an internal
algorithm. You can choose to stop AOC calibration when you are satisfied with the
result, or you can set up rolling (continuous) AOC calibration.
Procedure
•
To use the Compensation Off option:
a) Choose
Configure
>
Manual Setup
>
Inputs/Outputs
>
Batcher
>
Batcher
.
b) Set
Compensation Mode
to No Compensation.
•
To use the Fixed Compensation Value option:
a) Choose
Configure
>
Manual Setup
>
Inputs/Outputs
>
Batcher
>
Batcher
.
b) Set
Compensation Mode
to Fixed Value.
c) Set
Fixed AOC Value
to the quantity to be subtracted from the batch target.
Important
Adjust the fixed value:
—
Whenever the process changes (e.g., flow rate, process fluid)
—
Whenever you change any configuration parameter that can affect flow measurement (e.g., damping)
•
To use the AOC Algorithm option:
a) Choose
Configure
>
Manual Setup
>
Inputs/Outputs
>
Batcher
>
Batcher
.
b) Set
Compensation Mode
to AOC.
c) Perform AOC calibration.
Restriction
You cannot perform AOC calibration using the Field Communicator. AOC calibration requires running
several batches, and you cannot run batches using the Field Communicator.
Configuration and Use Manual
Configure process measurement applications
MMI-20025166
March 2019
Configuration and Use Manual
103