Field Communicator
Not available
The transmitter can write the current value of four totalizers or inventories to a log, at user-specified intervals.
You can generate a log file from this data for viewing and analysis.
Procedure
1. Specify the date on which totalizer logging will begin.
You must specify a future date. If you try to specify the current date, the transmitter will reject the
setting.
2. Specify the time at which totalizer logging will begin.
3. Specify the number of hours between records.
4. Select up to four totalizers or inventories to be logged.
6.7 Configure Process Variable Fault Action
Display
Menu
>
Configuration
>
Alert Setup
>
Output Fault Actions
ProLink III
Device Tools
>
Configuration
>
Fault Processing
Field Communicator
Configure
>
Alert Setup
>
Output Fault Actions
>
Channel E
>
Process Var Fault Action
Process Variable Fault Action
specifies the values that will be reported via the display and digital
communications if the device encounters a fault condition. The values are also sent to the outputs for
processing against their configured fault actions.
Procedure
Set
Process Variable Fault Action
as desired.
•
Default: None
Restriction
If you set
Process Variable Fault Action
to NAN, you cannot set
mA Output Fault Action
or
Frequency
Output Fault Action
to None. If you try to do this, the transmitter will not accept the configuration.
Important
•
If you want the mA Output to continue reporting process data during fault conditions, you must set both
Process Variable Fault Action
and
mA Output Fault Action
to
None
. If
mA Output Fault Action
is set to
None
and
Process Variable Fault Action
is set to any other option, the mA Output will produce the signal
associated with the selection.
•
If you want the Frequency Output to continue reporting process data during fault conditions, you must set
both
Process Variable Fault Action
and
Frequency Output Fault Action
to
None
. If
Frequency Output
Fault Action
is set to
None
and
Process Variable Fault Action
is set to any other option, the Frequency
Output will produce the signal associated with the selection.
Configure advanced options for process measurement
Configuration and Use Manual
March 2019
MMI-20025166
114
Micro Motion Model 5700 Transmitters with Configurable Outputs