
Status alarms and recommended actions
(continued)
Table 12-2:
Alarm code
Description
Recommended actions
A100
mA Output 1 Saturated
The calculated mA output value is outside of the meter's config-
ured range.
1. Check the
Upper Range Value
and
Lower Range Value
parame-
ters. Are they set correctly?
2. Check your process conditions against the values reported
by the flowmeter.
3. Verify that the measurement units are configured correctly
for your application.
4. Purge the flow tubes.
5. Verify process conditions, checking especially for air in the
flow tubes, tubes not filled, foreign material in the tubes, or
coating in the tubes.
A101
mA Output 1 Fixed
Non-zero HART address configured, or the mA output is config-
ured to send a constant value.
1. Check whether the output is in loop test mode. If it is, unfix
the output.
2. Exit mA output trim, if applicable.
3. Check the HART polling address.
4. Check whether the output has been set to a constant value
via digital communication.
A102
Drive Overrange
The drive power (current/voltage) is at its maximum.
1. Check the drive gain and pickoff voltage.
2. Check for electrical shorts between sensor terminals or be-
tween the sensor terminals and the sensor case.
3. Check for partially filled tubes, tube fouling, damaged tubes,
and excessive air entrainment or flashing.
4. Settling from a two- or three-phase fluid could create this
alarm even if the flow tubes are full, which could mean the
sensor needs to be reoriented. Refer to the sensor installa-
tion manual for recommended sensor orientations.
A103
Data Loss Possible (Totals and
Inventories)
The totalizers are not being saved properly. The core processor
was unable to store the totalizers on the last power-down and
must rely on the saved totals. The saved totals can be as much as
two hours out of date.
1. Make sure the transmitter and core processor are receiving
sufficient power.
2. Check the power supply and power supply wiring.
A104
Calibration in Progress
A calibration procedure is in process.
A105
Slug Flow
The density of the process has exceeded the user-defined densi-
ty limits. Check for slug flow (two-phase flow).
A106
Burst Mode Enabled
HART burst mode is enabled.
A107
Power Reset Occurred
The transmitter has been restarted.
A108
Basic Event 1 On
No action required.
A109
Basic Event 2 On
No action required.
Troubleshooting
Configuration and Use Manual
217
Summary of Contents for MICRO MOTION 2700
Page 10: ...Getting Started 2 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 14: ...Before you begin 6 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 26: ...Configuration and commissioning 18 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 84: ...Configure process measurement 76 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 214: ...Measurement support 206 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 258: ...Troubleshooting 250 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 354: ...Default values and ranges 346 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 373: ......