6.6
Configure digital communications
The digital communications parameters control how the transmitter will communicate
using digital communications.
Your transmitter supports the following types of digital communications:
•
HART/Bell 202 over the primary mA terminals
•
HART/RS-485 over the RS-485 terminals
•
Modbus/RS-485 over the RS-485 terminals
•
Modbus RTU via the service port
Note
The service port responds automatically to a wide range of connection requests. It is not
configurable.
6.6.1
Configure HART/Bell 202 communications
Display
OFF-LINE MAINT
>
OFF-LINE CONFG
>
COMM
ProLink II
ProLink
>
Configuration
>
Device
>
Digital Comm Settings
ProLink III
Device Tools
>
Configuration
>
Communications
>
Communications (HART)
Field Communicator
Configure
>
Manual Setup
>
Inputs/Outputs
>
Communications
>
HART Communications
Overview
HART/Bell 202 communications parameters support HART communication with the
transmitter's primary mA terminals over a HART/Bell 202 network.
The HART/Bell 202 communications parameters include:
•
HART Address
(
Polling Address
)
•
Loop Current Mode
(ProLink II) or
mA Output Action
(ProLink III)
•
Burst Parameters
(optional)
•
HART Variables
(optional)
Procedure
1.
Set
HART Address
to a unique value on your network.
Valid address values are between
0
and
15
. The default address (0) is typically used
unless you are in a multidrop environment.
Tip
Devices using HART protocol to communicate with the transmitter may use either
HART
Address
or
HART Tag
(
Software Tag
) to identify the transmitter. Configure either or both, as
required by your other HART devices.
Integrate the meter with the control system
124
Micro Motion
®
Model 2700 Transmitters with Analog Outputs
Summary of Contents for MICRO MOTION 2700
Page 10: ...Getting Started 2 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 14: ...Before you begin 6 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 26: ...Configuration and commissioning 18 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 84: ...Configure process measurement 76 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 214: ...Measurement support 206 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 258: ...Troubleshooting 250 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 354: ...Default values and ranges 346 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 373: ......