Overview
Frequency Output Process Variable
controls the variable that is reported over the frequency
output.
Prerequisites
If you plan to configure the output to report volume flow, ensure that you have set
Volume
Flow Type
as desired:
Liquid
or
Gas Standard Volume
.
If you plan to configure an output to report a concentration measurement process
variable, ensure that the concentration measurement application is configured so that the
desired variable is available.
If you are using the HART variables, be aware that changing the configuration of
Frequency
Output Process Variable
will change the configuration of the HART Tertiary Variable (TV).
Procedure
Set
Frequency Output Process Variable
as desired.
The default setting is
Mass Flow Rate
.
Options for Frequency Output Process Variable
The transmitter provides a basic set of options for
Frequency Output Process Variable
, plus
several application-specific options. Different communications tools may use different
labels for the options.
Options for Frequency Output Process Variable
Table 6-5:
Process variable
Label
Display
ProLink II
ProLink III
Field Communica-
tor
Standard
Mass flow
MFLOW
Mass Flow
Mass Flow Rate
Mass flo
Volume flow
VFLOW
Vol Flow
Volume Flow Rate
Vol flo
Gas standard volume flow rate
GSV F
Gas Std Vol Flow Rate
Gas Standard Volume
Flow Rate
Gas vol flo
Petroleum measurement
Temperature-corrected
(standard) volume flow
TCVOL
Std Vol Flow
Volume Flow Rate at
Reference Tempera-
ture
TC Vol
Concentration measurement
Standard volume flow
STD V
ED: Std Vol Flow Rate
Volume Flow Rate at
Reference Tempera-
ture
ED Std Vol flo
Integrate the meter with the control system
Configuration and Use Manual
109
Summary of Contents for MICRO MOTION 2700
Page 10: ...Getting Started 2 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 14: ...Before you begin 6 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 26: ...Configuration and commissioning 18 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 84: ...Configure process measurement 76 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 214: ...Measurement support 206 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 258: ...Troubleshooting 250 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 354: ...Default values and ranges 346 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 373: ......