Available actions when Approvals=
OIML
(continued)
Table 10-6:
Function
Transmitter status
Unsecured
Secured
Smart Meter Verification Outputs set to Continue
Measuring
Allowed
Allowed
Outputs set to Fault
Allowed
Allowed
Outputs set to Last Meas-
ured Value
Allowed
Not allowed
External pressure and
temperature data
Retrieved by polling
Allowed
Allowed
Written by Modbus or
HART host
Allowed
Not allowed
Outputs
mA output loop test
Allowed
Not allowed
mA output trim
Allowed
Not allowed
Frequency output loop
test
Allowed
Not allowed
Discrete output loop test Allowed
Not allowed
Process variables
All flow rates
Reported normally
Reported normally
Density
Reported normally
Reported normally
Temperature
Reported normally
Reported normally
Totalizers
Resetting
Allowed. If any single to-
talizer is reset, all other
totalizers are reset auto-
matically.
May or may not be allowed, depend-
ing on configuration. Can be per-
formed only if flow rate is zero. If any
single totalizer is reset, all other total-
izers are reset automatically.
Starting
Not allowed
N/A
Stopping
N/A
Not allowed
Inventories
Resetting
Allowed
Not allowed
Sensor simulation
Allowed
Not allowed
10.2
Switch between secured and unsecured mode
You must switch to unsecured mode to change the transmitter configuration or perform
many administrative tasks. You must switch back to secured mode in order to meet
Weights & Measures requirements for process measurement.
You must use one of the following tools to switch modes:
•
ProLink II
•
ProLink III
•
The Custody Transfer “switching” utility. The switching utility is free, and is available
from the Micro Motion web site:
www.micromotion.com/softwaredownloads
.
Operate the transmitter with the Weights & Measures application
168
Micro Motion
®
Model 2700 Transmitters with Analog Outputs
Summary of Contents for MICRO MOTION 2700
Page 10: ...Getting Started 2 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 14: ...Before you begin 6 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 26: ...Configuration and commissioning 18 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 84: ...Configure process measurement 76 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 214: ...Measurement support 206 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 258: ...Troubleshooting 250 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 354: ...Default values and ranges 346 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 373: ......