2.4
Characterize the flowmeter (if required)
Display
Not available
ProLink II
•
ProLink
>
Configuration
>
Device
>
Sensor Type
•
ProLink
>
Configuration
>
Flow
•
ProLink
>
Configuration
>
Density
•
ProLink
>
Configuration
>
T Series
ProLink III
Device Tools
>
Calibration Data
Field Communicator
Configure
>
Manual Setup
>
Characterize
Overview
Characterizing the flowmeter adjusts your transmitter to match the unique traits of the
sensor it is paired with. The characterization parameters (also called calibration
parameters) describe the sensor’s sensitivity to flow, density, and temperature.
Depending on your sensor type, different parameters are required. Values for your sensor
are provided by Micro Motion on the sensor tag or the calibration certificate.
Tip
If your flowmeter was ordered as a unit, it has already been characterized at the factory. However,
you should still verify the characterization parameters.
Procedure
1.
Specify
Sensor Type
.
•
Straight-tube
(T-Series)
•
Curved-tube
(all sensors except T-Series)
2.
Set the flow characterization parameters. Be sure to include all decimal points.
•
For straight-tube sensors, set
FCF
(
Flow Cal
or
Flow Calibration Factor
),
FTG
, and
FFQ
.
•
For curved-tube sensors, set
Flow Cal
(
Flow Calibration Factor
).
3.
Set the density characterization parameters.
•
For straight-tube sensors, set
D1
,
D2
,
DT
,
DTG
,
K1
,
K2
,
FD
,
DFQ1
, and
DFQ2
.
•
For curved-tube sensors, set
D1
,
D2
,
TC
,
K1
,
K2
, and
FD
. (
TC
is sometimes shown
as
DT
.)
2.4.1
Sources and formats for characterization parameters
Different sensor tags display characterization parameters differently. On older sensors, the
sensor tag may not contain all the required parameters.
Sample sensor tags
Sample sensor tags are shown in the following illustrations:
Quick start
10
Micro Motion
®
Model 2700 Transmitters with Analog Outputs
Summary of Contents for MICRO MOTION 2700
Page 10: ...Getting Started 2 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 14: ...Before you begin 6 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 26: ...Configuration and commissioning 18 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 84: ...Configure process measurement 76 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 214: ...Measurement support 206 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 258: ...Troubleshooting 250 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 354: ...Default values and ranges 346 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 373: ......