IQ 150S C: DNP Map
Maximum Demands of Total Power (Points 15 - 19)
These points are formatted as 2's complement fractions. They represent a fraction of 4500W Sec-
ondary in normal operation, or 3000W Secondary in Open Delta operation. Inputs above/below +/-
4500 or +/-3000W Secondary are pinned at +/-4500 or +/-3000W Secondary, respectively.
Phase Angle (Points 20 - 25)
These points are formatted as 2's complement integers. They represent angles from -180.00
(0x0F8F8) to +180.00 (0x00708).
CT & PT Ratios (Points 26 - 31)
Point
Reading
15
Maximum Positive Demand Total Watts
16
Maximum Positive Demand Total VARs
17
Maximum Negative Demand Total Watts
18
Maximum Negative Demand Total VARs
19
Maximum Average Demand VAs
Point
Reading
20
Phase A Current Angle
21
Phase B Current Angle
22
Phase C Current Angle
23
Volts A-B Angle
24
Volts B-C Angle
25
Volts C-A Angle
Point
Reading
26
CT Ratio Numerator
27
CT Ratio Multiplier
28
CT Ratio Denominator
29
PT Ratio Numerator
30
PT Ratio Multiplier
Summary of Contents for IQ 150S
Page 4: ......
Page 14: ...IM02601006E www eaton com 1 4 IQ 150S 250S 1 Introduction This page intentionally left blank...
Page 93: ...IM02601006E www eaton com 5 43 IQ 150S 250S 5 Communication XY Graph Advanced Graph...
Page 116: ...IM02601006E www eaton com 5 66 IQ 150S 250S 5 Communication This page intentionally left blank...
Page 192: ...IQ 150S B Modbus Map IM02601006E www eaton com MM 10 This page intentionally left blank...
Page 208: ...IQ 250S B Modbus Map IM02601006E www eaton com MM 16 This page intentionally left blank...
Page 222: ...IM02601006E www eaton com C 14 IQ 150S C DNP Map This page intentionally left blank...
Page 234: ...IM02601006E www eaton com D 10 IQ 250S D DNP Map This page intentionally left blank...