• Records Used: The number of records stored in the log. This number will equal the Max Records
when the log has filled. This value will be set to 1 when the log is reset. The data type is an
unsigned integer from 1 - 2^32.
NOTE:
The first record in every log before it has rolled over is a "dummy" record, filled with all
0xFF's. When the log is filled and rolls over, this record is overwritten.
• Record Size: The number of bytes in this record, including the timestamp. The data type is an
unsigned integer in the range of 14 - 242.
• Log Availability: A flag indicating if the log is available for retrieval, or if it is in use by another
port.
0
Log Available for retrieval
1
Not used
2
In use by COM2 (RS485)
0xFFFF
Log Not Available - the log cannot be retrieved.
This indicates that the log is disabled.
NOTE:
To query the port by which you are currently connected, use the Port ID register:
Register:
0x1193
Size:
1 register
Description: A value from 1-4, which enumerates the port that the requestor is currently con-
nected on.
NOTES:
• When Log Retrieval is engaged, the Log Availability value will be set to the port that engaged
the log. The Log Availability value will stay the same until either the log has been disen-
gaged, or 5 minutes have passed with no activity. It will then reset to 0 (available).
• Each log can only be retrieved by one port at a time.
• Only one log at a time can be retrieved.
• First Timestamp: Timestamp of the oldest record.
Summary of Contents for IQ 150S
Page 4: ......
Page 14: ...IM02601006E www eaton com 1 4 IQ 150S 250S 1 Introduction This page intentionally left blank...
Page 93: ...IM02601006E www eaton com 5 43 IQ 150S 250S 5 Communication XY Graph Advanced Graph...
Page 116: ...IM02601006E www eaton com 5 66 IQ 150S 250S 5 Communication This page intentionally left blank...
Page 192: ...IQ 150S B Modbus Map IM02601006E www eaton com MM 10 This page intentionally left blank...