IM02601006E www.eaton.com C-7
IQ 150S C: DNP Map
C.5.1.3: 32-Bit Binary Counter Without Flag (Obj. 20, Var. 5)
Counters support the following functions:
Read (Function 1)
A READ request for Variation 0 is responded to with Variation 5.
Counters are used to communicate the following data measured by IQ 150S/250S meters:
Hour Readings
Hour Readings (Points 0 - 4)
NOTE:
These readings may be cleared by using the Control Relay Output Block (see previous
Section C.5.1.2).
C.5.1.4: 16-Bit Analog Input Without Flag (Obj. 30, Var. 4)
Analog Inputs support the following functions:
Read (Function 1)
A READ request for Variation 0 is responded to with Variation 4.
Analog Inputs are used to communicate the following data measured by IQ 150S meters:
• Health Check
• Phase-to-Neutral Voltage
• Phase-to-Phase Voltage
• Phase Current
Point
Readings
Unit
0
+W hour
Wh
1
-W hour
Wh
2
+VAR hour
VARh
3
-VAR hour
VARh
4
+VA hour
VAh
Summary of Contents for IQ 150S
Page 4: ......
Page 14: ...IM02601006E www eaton com 1 4 IQ 150S 250S 1 Introduction This page intentionally left blank...
Page 93: ...IM02601006E www eaton com 5 43 IQ 150S 250S 5 Communication XY Graph Advanced Graph...
Page 116: ...IM02601006E www eaton com 5 66 IQ 150S 250S 5 Communication This page intentionally left blank...
Page 192: ...IQ 150S B Modbus Map IM02601006E www eaton com MM 10 This page intentionally left blank...
Page 208: ...IQ 250S B Modbus Map IM02601006E www eaton com MM 16 This page intentionally left blank...
Page 222: ...IM02601006E www eaton com C 14 IQ 150S C DNP Map This page intentionally left blank...
Page 234: ...IM02601006E www eaton com D 10 IQ 250S D DNP Map This page intentionally left blank...