IQ 150S C: DNP Map
C.5.1.5: Class 0 Data (Obj. 60, Var. 1)
Class 0 Data supports the following functions:
Read (Function 1)
A request for Class 0 Data from a IQ 150S meter returns three Object Headers. Specifically, it
returns 16-Bit Analog Input Without Flags (Object 30, Variation 4), Points 0 - 31, followed by 32-Bit
Counters Without Flags (Object 20, Variation 5), Points 0 - 4, followed by Binary Output Status
(Object 10, Variation 2), Points 0 - 1. (There is NO Object 1.)
A request for Object 60, Variation 0 is treated as a request for Class 0 Data.
C.5.1.6: Internal Indications (Obj. 80, Var. 1)
Internal Indications support the following functions:
Write (Function 2)
Internal Indications may be indexed by Qualifier Code 0.
Device Restart (Point 0)
This bit is set whenever the meter resets. The polling device may clear this bit by Writing (Function
2) to Object 80, Point 0.
C.6: IQ 150S Meter DNP Mapping (DNP-1 to DNP-2)
The IQ 150S DNP Point Map follows.
Binary Output States, Control Relay Outputs, Binary Counters (Primary) and Analog Inputs are
described on Page 1.
Internal Indication is described on Page 2.
Summary of Contents for IQ 150S
Page 4: ......
Page 14: ...IM02601006E www eaton com 1 4 IQ 150S 250S 1 Introduction This page intentionally left blank...
Page 93: ...IM02601006E www eaton com 5 43 IQ 150S 250S 5 Communication XY Graph Advanced Graph...
Page 116: ...IM02601006E www eaton com 5 66 IQ 150S 250S 5 Communication This page intentionally left blank...
Page 192: ...IQ 150S B Modbus Map IM02601006E www eaton com MM 10 This page intentionally left blank...
Page 208: ...IQ 250S B Modbus Map IM02601006E www eaton com MM 16 This page intentionally left blank...
Page 222: ...IM02601006E www eaton com C 14 IQ 150S C DNP Map This page intentionally left blank...
Page 234: ...IM02601006E www eaton com D 10 IQ 250S D DNP Map This page intentionally left blank...